3-20
Programming and Parameters
No. Parameter Name and Description
168 [Start At PowerUp]
Enables/disables a feature to issue a
Start or Run command and automatically
resume running at commanded speed
after drive input power is restored.
Requires a digital input configured for Run
or Start and a valid start contact.
!
169 [Flying Start En]
Enables/disables the function which
reconnects to a spinning motor at actual
RPM when a start command is issued.
170 [Flying StartGain]
Sets the response of the flying start
function.
174 [Auto Rstrt Tries]
Sets the maximum number of times the
drive attempts to reset a fault and restart.
!
175 [Auto Rstrt Delay]
Sets the time between restart attempts
when [Auto Rstrt Tries] is set to a value
other than zero.
184 [Power Loss Mode]
Sets the reaction to a loss of input power.
Power loss is recognized when:
• DC bus voltage is ≤ 73% of [DC Bus
Memory] and [Power Loss Mode] is
set to "Coast".
• DC bus voltage is ≤ 82% of [DC Bus
Memory] and [Power Loss Mode] is
set to "Decel"
185 [Power Loss Time]
Sets the time that the drive will remain in
power loss mode before a fault is issued.
ATTENTION: Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application. Do
not use this function without considering applicable local, national
and international codes, standards, regulations or industry
guidelines.
ATTENTION: Equipment damage and/or personal injury may
result if this parameter is used in an inappropriate application. Do
not use this function without considering applicable local, national
and international codes, standards, regulations or industry
guidelines.
Values
Default:
0
"Disabled"
Options:
0
"Disabled"
1
"Enabled"
Default:
0
"Disabled"
Options:
0
"Disabled"
1
"Enabled"
Default:
4000
Min/Max:
20/32767
Display:
1
Default:
0
Min/Max:
0/9
Display:
1
Default:
1.0 Secs
Min/Max:
0.5/30.0 Secs
Display:
0.1 Secs
Default:
0
"Coast"
Options:
0
"Coast"
1
"Decel"
Default:
0.5 Secs
Min/Max:
0.0/60.0 Secs
Display:
0.1 Secs
170
169
175
174