4-6
Troubleshooting
Fault
No.
Pwr Brd Chksum2 105
Replaced
107
MCB-PB
Shear Pin
63
SW OverCurrent
36
Trnsistr OvrTemp 9
UnderVoltage
4
UserSet1 Chksum 101
UserSet2 Chksum 102
UserSet3 Chksum 103
(1)
See
page 4-1
for a description of fault types.
Description
➁
The checksum read from the
board does not match the
checksum calculated.
➁
Main Control Board was replaced
and parameters were not
programmed.
➂
Programmed [Current Lmt Val]
has been exceeded. Enable/
Disable with [Fault Config 1] on
page
3-27.
➀
The drive output current has
exceeded the hardware current.
➀
Output transistors have
exceeded their maximum
operating temperature.
➀
DC bus voltage fell below the
minimum value of 407V DC at
➂
400/480V input or 204V DC at
200/240V input. Enable/Disable
with [Fault Config 1] on
page
3-27.
➁
The checksum read from the
user set does not match the
➁
checksum calculated.
➁
Action
1. Cycle power to the drive.
2. If problem persists, replace drive.
1. Restore defaults.
2. Reprogram parameters.
Check load requirements and
[Current Lmt Val] setting.
Check for excess load, improper DC
boost setting. DC brake volts set too
high.
1. Check for blocked or dirty heat
sink fins. Verify that ambient
temperature has not exceeded
40°C (104°F) for IP 20 (NEMA Type
1) installations or 50°C (122°F) for
Open type installations.
2. Check fan.
Monitor the incoming AC line for low
voltage or power interruption.
Re-save user set.