4-8
Troubleshooting
Alarm
Dig In ConflictA
Dig In ConflictB
Dig In ConflictC
Drive OL Level 1
Drive OL Level 2
FluxAmpsRef
Rang
IntDBRes
OvrHeat
Description
Digital input functions are in conflict. Combinations marked with a " " will
cause an alarm.
Acc2/Dec2 Accel 2
Acc2 / Dec2
Accel 2
Decel 2
Jog
Jog Fwd
Jog Rev
Fwd / Rev
Digital input functions are in conflict. Combinations marked with a " " will
cause an alarm.
Start Stop–CF Run Run Fwd Run Rev Jog Jog Fwd Jog Rev
Start
Stop–CF
Run
Run Fwd
Run Rev
Jog
Jog Fwd
Jog Rev
Fwd /
Rev
More than one physical input has been configured to the same input function.
Multiple configurations are not allowed for the following input functions.
Forward/Reverse
Speed Select 1
Speed Select 2
Speed Select 3
Run Forward
The calculated IGBT temperature requires a reduction in PWM frequency. If
[Drive OL Mode] is disabled and the load is not reduced, an overload fault will
eventually occur.
The calculated IGBT temperature requires a reduction in Current Limit. If
[Drive OL Mode] is disabled and the load is not reduced, an overload fault will
eventually occur.
The calculated or measured Flux Amps value is not within the expected
range. Verify motor data and rerun motor tests.
The drive has temporarily disabled the DB regulator because the resistor
temperature has exceeded a predetermined value.
Decel 2
Jog Jog Fwd Jog Rev Fwd/Rev
Run Reverse
Bus Regulation Mode B
Jog Forward
Acc2 / Dec2
Jog Reverse
Accel 2
Run
Decel 2
Stop Mode B
Fwd/
Rev