3-30
Programming and Parameters
No. Parameter Name and Description
276 [Logic Mask]
Determines which adapters can control the drive. If the bit for an adapter is set to
"0," the adapter will have no control functions except for stop.
Bit #
Factory Default Bit Values
277 [Start Mask]
Controls which adapters can issue start
commands.
278 [Jog Mask]
Controls which adapters can issue jog
commands.
279 [Direction Mask]
Controls which adapters can issue
forward/reverse direction commands.
280 [Reference Mask]
Controls which adapters can select an
alternate reference; [Speed Ref A, B Sel]
or [Preset Speed 1-7].
281 [Accel Mask]
Controls which adapters can select [Accel
Time 1, 2].
282 [Decel Mask]
Controls which adapters can select [Decel
Time 1, 2].
283 [Fault Clr Mask]
Controls which adapters can clear a fault.
284 [MOP Mask]
Controls which adapters can issue MOP
commands to the drive.
285 [Local Mask]
Controls which adapters are allowed to
take exclusive control of drive logic
commands (except stop). Exclusive
"local" control can only be taken while the
drive is stopped.
x
x
x
x
x
x
x
15
14
13
12
11
10
9
Nibble 4
Nibble 3
Values
x
x
x
1
x
1
1
1
8
7
6
5
4
3
2
1
Nibble 2
Nibble 1
1
1 =Control Permitted
0 =Control Masked
0
x =Reserved
See
[Logic
Mask].
See
[Logic
Mask].
See
[Logic
Mask].
See
[Logic
Mask].
See
[Logic
Mask].
See
[Logic
Mask].
See
[Logic
Mask].
See
[Logic
Mask].
See
[Logic
Mask].
288
thru
297
288
thru
297
288
thru
297
288
thru
297
288
thru
297
288
thru
297
288
thru
297
288
thru
297
288
thru
297
288
thru
297

Hide quick links: