5.2 PRODUCT SETUP

5.2PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
PASSWORD
SECURITY
5
Two levels of password security are provided: Command and Setting. Operations under password supervision are:
COMMAND:
operating the breakers via faceplate keypad, changing the state of virtual inputs, clearing the event
records, clearing the oscillography records, clearing fault reports, changing the date and time, clearing
the breaker arcing current, clearing the data logger, user-programmable pushbuttons
SETTING:
changing any setting, test mode operation
The Command and Setting passwords are defaulted to "Null" when the relay is shipped from the factory. When a password
is set to "Null", the password security feature is disabled.
Programming a password code is required to enable each access level. A password consists of 1 to 10 numerical charac-
ters. When a
CHANGE ... PASSWORD
1.
ENTER NEW PASSWORD: ____________
2.
VERIFY NEW PASSWORD: ____________
3.
NEW PASSWORD HAS BEEN STORED
To gain write access to a "Restricted" setting, set
change the setting and follow the prompt to enter the programmed password. If the password is correctly entered, access
will be allowed. If no keys are pressed for longer than 30 minutes or control power is cycled, accessibility will automatically
revert to the "Restricted" level.
If an entered password is lost (or forgotten), consult the factory with the corresponding
In the event that an incorrect Command or Setting password has been entered via the faceplate interface three times within
a three-minute time span, the
Settings or Command access via the faceplate interface for the next ten minutes. The
flash message will appear upon activation of the ten minute timeout or any other time a user attempts any
FOR 10 MIN!
change to the defined tier during the ten minute timeout. The
"Off" after the expiration of the ten-minute timeout.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the
the D30 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The
REMOTE ACCESS DENIED
The D30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
The
UNAUTHORIZED ACCESS
command. Therefore, to apply this feature with security, the command level should be password-protected.
ALARMS
The operand does not generate events or targets. If these are required, the operand can be assigned to a digital element
programmed with event logs and/or targets enabled.
5-8

PASSWORD SECURITY

ACCESS LEVEL:
Restricted
CHANGE COMMAND
MESSAGE
PASSWORD: No
CHANGE SETTING
MESSAGE
PASSWORD: No
ENCRYPTED COMMAND
MESSAGE
PASSWORD: ----------
ENCRYPTED SETTING
MESSAGE
PASSWORD: ----------
setting is set to "Yes", the following message sequence is invoked:
ACCESS LEVEL
LOCAL ACCESS DENIED
FlexLogic™ operand will be set to "Off" after the expiration of the ten-minute timeout.
operand is reset with the
D30 Line Distance Relay
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
Range: No, Yes
Range: No, Yes
Range: 0 to 9999999999
Note: ---------- indicates no password
Range: 0 to 9999999999
Note: ---------- indicates no password
to "Setting" and then change the setting, or attempt to
FlexLogic™ operand will be set to "On" and the D30 will not allow
LOCAL ACCESS DENIED
FlexLogic™ operand will be set to "On" and
REMOTE ACCESS DENIED
UNAUTHORIZED ACCESS
COMMANDS
CLEAR RECORDS
5 SETTINGS
5.2.1 PASSWORD SECURITY
.
ENCRYPTED PASSWORD
TOO MANY ATTEMPTS – BLOCKED
FlexLogic™ operand will be set to
FlexLogic™ operand is
RESET UNAUTHORIZED