Type Tests; Production Tests; Approvals; Maintenance - GE D30 Instruction Manual

Line distance
Hide thumbs Also See for D30:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
Electrical fast transient: ANSI/IEEE C37.90.1
IEC 61000-4-4
IEC 60255-22-4
Oscillatory transient:
ANSI/IEEE C37.90.1
IEC 61000-4-12
Insulation resistance:
IEC 60255-5
Dielectric strength:
IEC 60255-6
ANSI/IEEE C37.90
Electrostatic discharge: EN 61000-4-2
Surge immunity:
EN 61000-4-5
RFI susceptibility:
ANSI/IEEE C37.90.2
IEC 61000-4-3
IEC 60255-22-3
Ontario Hydro C-5047-77
Conducted RFI:
IEC 61000-4-6
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.

APPROVALS

UL Listed for the USA and Canada
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds)
of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust
has accumulated on the faceplate display, a dry cloth can be used.
GE Multilin
Voltage dips/interruptions/variations:
Power frequency magnetic field immunity:
Pulse magnetic field immunity: IEC 61000-4-9
Vibration test (sinusoidal): IEC 60255-21-1
Shock and bump:
Seismic:
Cold:
Dry heat:
Type test report available upon request.
NOTE
CE:
LVD 73/23/EEC:
EMC 81/336/EEC:
Units that are stored in a de-energized state should be
powered up once per year, for one hour continuously, to
NOTE
avoid deterioration of electrolytic capacitors.
D30 Line Distance Relay
2.2 SPECIFICATIONS

2.2.11 TYPE TESTS

IEC 61000-4-11
IEC 60255-11
IEC 61000-4-8
IEC 60255-21-2
IEC 60255-21-3
IEEE C37.98
IEC 60028-2-1, 16 h at –40°C
IEC 60028-2-2, 16 h at 85°C

2.2.12 PRODUCTION TESTS

2.2.13 APPROVALS
IEC 1010-1
EN 50081-2, EN 50082-2

2.2.14 MAINTENANCE

2
2-17

Advertisement

Table of Contents
loading

Table of Contents