5 SETTINGS

5.5GROUPED ELEMENTS

Each protection element can be assigned up to six different sets of settings according to Setting Group designations 1 to 6.
The performance of these elements is defined by the active Setting Group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (e.g. altered power system configuration,
season of the year). The active setting group can be preset or selected via the
ments section later in this chapter). See also the Introduction to Elements section at the beginning of this chapter.
PATH: SETTINGS
GROUPED ELEMENTS

SETTING GROUP 1

MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Each of the six setting group menus is identical.
no other group is active (see the Control Elements section for additional details).
GE Multilin
SETTING GROUP 1(6)
LINE PICKUP
DISTANCE
POWER SWING
DETECT
LOAD ENCROACHMENT
PHASE CURRENT
NEUTRAL CURRENT
GROUND CURRENT
NEGATIVE SEQUENCE
CURRENT
VOLTAGE ELEMENTS
(the default active group) automatically becomes active if
SETTING GROUP 1
D30 Line Distance Relay
5.5 GROUPED ELEMENTS

5.5.1 OVERVIEW

menu (see the Control Ele-
SETTING GROUPS
5.5.2 SETTING GROUP
See page 5-86.