Breakers - GE D30 Instruction Manual

Line distance
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.3 SYSTEM SETUP
PATH: SETTINGS
SYSTEM SETUP
BREAKER 1
5
A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Only informa-
tion concerning programming of the associated settings is covered here. These features are provided for two breakers; a
user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
BREAKER 1(2) FUNCTION: Set to "Enable" to allow the operation of any breaker control feature.
BREAKER1(2) PUSH BUTTON CONTROL: Set to "Enable" to allow faceplate push button operations.
BREAKER 1(2) NAME: Assign a user-defined name (up to six characters) to the breaker. This name will be used in
flash messages related to breaker 1.
BREAKER 1(2) MODE: Selects "3-pole" mode, where all breaker poles are operated simultaneously, or "1-pole" mode
where all breaker poles are operated either independently or simultaneously.
BREAKER 1(2) OPEN: Selects an operand that creates a programmable signal to operate an output relay to open
Breaker No. 1.
BREAKER 1(2) CLOSE: Selects an operand that creates a programmable signal to operate an output relay to close
Breaker No. 1.
BREAKER 1(2) ΦA/3-POLE: Selects an operand, usually a contact input connected to a breaker auxiliary position
tracking mechanism. This input can be either a 52/a or 52/b contact, or a combination the 52/a and 52/b contacts, that
must be programmed to create a logic 0 when the breaker is open. If
ting selects a single input as the operand used to track the breaker open or closed position. If the mode is selected as
5-56

BREAKERS

BREAKER 1
FUNCTION: Disabled
BREAKER1 PUSH BUTTON
MESSAGE
CONTROL: Disabled
BREAKER 1 NAME:
MESSAGE
Bkr 1
BREAKER 1 MODE:
MESSAGE
3-Pole
BREAKER 1 OPEN:
MESSAGE
Off
BREAKER 1 CLOSE:
MESSAGE
Off
BREAKER 1 φA/3-POLE:
MESSAGE
Off
BREAKER 1 φB:
MESSAGE
Off
BREAKER 1 φC:
MESSAGE
Off
BREAKER 1 EXT ALARM:
MESSAGE
Off
BREAKER 1 ALARM
MESSAGE
DELAY:
MANUAL CLOSE RECAL1
MESSAGE
TIME:
BREAKER 1 OUT OF SV:
MESSAGE
Off
D30 Line Distance Relay
BREAKER 1(2)
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to 6 alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 1 000 000.000 s in steps of 0.001
0.000 s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
0.000 s
Range: FlexLogic™ operand
BREAKER 1 MODE
5 SETTINGS
5.3.4 BREAKERS
is selected as "3-Pole", this set-
GE Multilin