Event Records; Oscillography - GE D30 Instruction Manual

Line distance
Hide thumbs Also See for D30:
Table of Contents

Advertisement

6 ACTUAL VALUES
PATH: ACTUAL VALUES
RECORDS

EVENT RECORDS

MESSAGE
MESSAGE
MESSAGE
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. Refer to the
COMMANDS
PATH: ACTUAL VALUES
RECORDS

OSCILLOGRAPHY

MESSAGE
MESSAGE
MESSAGE
MESSAGE
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
'cycles per record' value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillogra-
phy section of Chapter 5 for further details.
A trigger can be forced here at any time by setting "Yes" to the
menu for clearing the oscillography records.
CLEAR RECORDS
GE Multilin
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
menu for clearing event records.
CLEAR RECORDS
OSCILLOGRAPHY
FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
CYCLES PER RECORD:
0.0
LAST CLEARED DATE:
2000/07/14
15:40:16
FORCE TRIGGER?
D30 Line Distance Relay
6.4.2 EVENT RECORDS
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps
6.4.3 OSCILLOGRAPHY
Range: No, Yes
command. Refer to the
6.4 RECORDS
6
COMMANDS
6-21

Advertisement

Table of Contents
loading

Table of Contents