3 HARDWARE
Figure 3–10: ZERO-SEQUENCE CORE BALANCE CT INSTALLATION
The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as
input for the synchrocheck and volts-per-hertz features.
Substitute the tilde "~" symbol with the slot position of the module in the following figure.
NOTE
GE Multilin
UNSHIELDED CABLE
Ground connection to neutral
must be on the source side
Source
A
B
C
N
G
Ground
outside CT
LOAD
Current inputs
8F and 8G modules (4 CTs and 4 VTs)
Figure 3–11: CT/VT MODULE WIRING
D30 Line Distance Relay
SHIELDED CABLE
Stress cone
Source
A
B
C
To ground;
LOAD
must be on
load side
996630A5
Voltage inputs
842768A1.CDR
3.2 WIRING
shields
3
3-9