APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 46)
ADDR
REGISTER NAME
71FA
Line Pickup Block
71FB
Line Pickup Target
71FC
Line Pickup Events
71FD
Terminal Open
71FE
Autoreclose Accelerate
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260
Phase Directional Overcurrent 1 Function
7261
Phase Directional Overcurrent 1 Source
7262
Phase Directional Overcurrent 1 Block
7263
Phase Directional Overcurrent 1 ECA
7264
Phase Directional Overcurrent 1 Pol V Threshold
7265
Phase Directional Overcurrent 1 Block Overcurrent
7266
Phase Directional Overcurrent 1 Target
7267
Phase Directional Overcurrent 1 Events
7268
Reserved (8 items)
7270
...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7280
Neutral Directional Overcurrent 1 Function
7281
Neutral Directional Overcurrent 1 Source
7282
Neutral Directional Overcurrent 1 Polarizing
7283
Neutral Directional Overcurrent 1 Forward ECA
7284
Neutral Directional Overcurrent 1 Forward Limit Angle
7285
Neutral Directional Overcurrent 1 Forward Pickup
7286
Neutral Directional Overcurrent 1 Reverse Limit Angle
7287
Neutral Directional Overcurrent 1 Reverse Pickup
7288
Neutral Directional Overcurrent 1 Target
7289
Neutral Directional Overcurrent 1 Block
728A
Neutral Directional Overcurrent 1 Events
728B
Neutral Directional Overcurrent 1 Polarizing Voltage
728C
Neutral Directional Overcurrent 1 Op Current
728D
Neutral Directional Overcurrent 1 Offset
728E
Neutral Directional Overcurrent 1 Pos Seq Restraint
728F
Reserved
7290
...Repeated for Neutral Directional Overcurrent 2
Negative Sequence Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
72A0
Negative Sequence Directional Overcurrent 1 Function
72A1
Negative Sequence Directional Overcurrent 1 Source
72A2
Negative Sequence Directional Overcurrent 1 Type
72A3
Neg Sequence Directional Overcurrent 1 Forward ECA
72A4
Neg Seq Directional Overcurrent 1 Forward Limit Angle
72A5
Neg Sequence Directional Overcurrent 1 Forward Pickup
72A6
Neg Seq Directional Overcurrent 1 Reverse Limit Angle
72A7
Neg Sequence Directional Overcurrent 1 Reverse Pickup
72A8
Negative Sequence Directional Overcurrent 1 Target
72A9
Negative Sequence Directional Overcurrent 1 Block
72AA
Negative Sequence Directional Overcurrent 1 Events
72AB
Negative Sequence Directional Overcurrent 1 Offset
72AC
Neg Seq Directional Overcurrent 1 Pos Seq Restraint
72AD
Reserved (3 items)
72B0
...Repeated for Neg Seq Directional Overcurrent 2
Breaker Arcing Current Settings (Read/Write Setting) (2 modules)
72C0
Breaker 1 Arcing Current Function
72C1
Breaker 1 Arcing Current Source
72C2
Breaker 1 Arcing Current Initiate A
GE Multilin
RANGE
0 to 65535
0 to 2
0 to 1
0 to 65535
0 to 65535
0 to 1
0 to 5
0 to 65535
0 to 359
0 to 3
0 to 1
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 2
-90 to 90
40 to 90
degrees
0.002 to 30
40 to 90
degrees
0.002 to 30
0 to 2
0 to 65535
0 to 1
0 to 1
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
0 to 5
0 to 1
0 to 90
40 to 90
degrees
0.05 to 30
40 to 90
degrees
0.05 to 30
0 to 2
0 to 65535
0 to 1
0 to 250
0 to 0.5
0 to 1
0 to 1
0 to 5
0 to 65535
D30 Line Distance Relay
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F102
---
1
F167
---
1
F300
---
1
F001
pu
0.001
F001
---
1
F126
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F230
° Lag
1
F002
1
F001
pu
0.001
F001
1
F001
pu
0.001
F001
---
1
F109
---
1
F300
---
1
F102
---
1
F231
0 (Calculated V0)
---
1
F196
0 (Calculated 3I0)
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
1
F167
---
1
F179
0 (Neg Sequence)
° Lag
1
F002
1
F001
pu
0.01
F001
1
F001
pu
0.01
F001
---
1
F109
---
1
F300
---
1
F102
ohms
0.01
F001
---
0.001
F001
---
1
F001
---
1
F102
---
1
F167
---
1
F300
DEFAULT
0
0 (Self-reset)
0 (Disabled)
0
0
B
0 (Disabled)
0 (SRC 1)
0
30
700
0 (No)
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Voltage)
75
90
50
90
50
0 (Self-reset)
0
0 (Disabled)
0
63
0
0 (Disabled)
0 (SRC 1)
75
90
5
90
5
0 (Self-reset)
0
0 (Disabled)
0
63
0
0 (Disabled)
0 (SRC 1)
0