Product Setup; Security - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP

5.2PRODUCT SETUP
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 SECURITY
Two levels of password security are provided via the
is not available and intended for factory use only.
The following operations are under command password supervision:
Operating the breakers via faceplate keypad.
Changing the state of virtual inputs.
5
Clearing the event records.
Clearing the oscillography records.
Clearing fault reports.
Changing the date and time.
Clearing the breaker arcing current.
Clearing the data logger.
Clearing the user-programmable pushbutton states.
The following operations are under setting password supervision:
Changing any setting.
Test mode operation.
The command and setting passwords are defaulted to "0" when the relay is shipped from the factory. When a password is
set to "0", the password security feature is disabled.
The D30 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the D30, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The
PASSWORD ACCESS EVENTS
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
5-8

SECURITY

ACCESS LEVEL:
Restricted
 CHANGE LOCAL
MESSAGE
 PASSWORDS
 ACCESS
MESSAGE
 SUPERVISION
 DUAL PERMISSION
MESSAGE
 SECURITY ACCESS
PASSWORD ACCESS
MESSAGE
EVENTS: Disabled
settings allows recording of password access events in the event recorder.
D30 Line Distance Protection System
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
See page 5–9.
See page 5–10.
See page 5–11.
Range: Disabled, Enabled
setting: command and setting. The factory service level
ACCESS LEVEL
5 SETTINGS
5.2.1 SECURITY
GE Multilin