5-3

DST1-MRD08SL-1

5-3-1

Safety Input Specifications

5-3-2
Test Output Specifications
5-3-3

Safety Output Specifications for Relay Outputs

Relays
Failure rate P level (See note.) (Refer-
ence value)
Rated load for a resistive load
Durability
Note
The following table gives the safety input specifications for the DST1-
MRD08SL-1.
Item
Input type
ON voltage
OFF voltage
OFF current
Input current
The following table gives the test output specifications for the DST1-
MRD08SL-1.
Item
Output type
Rated output current
Residual voltage
Leakage current
The following table gives the safety output specifications for the DST1-
MRD08SL-1.
Item
Mechanical life
expectancy
Electrical life
expectancy
This value applies to a switching frequency of 300 operations/min.
Sinking input (PNP)
11 VDC min. between each input termi-
nal and G0
5 VDC max. between each input termi-
nal and G0
1 mA max.
6 mA
Sourcing output (PNP)
0.7 A
1.2 V max. between each output termi-
nal and V0
0.1 mA max.
Specifications
G7SA-2A2B
EN50205 Class A
1 mA at 5 VDC
240 VAC: 2 A
30 VDC: 2 A
5,000,000 operations min.
(at approx. 7,200 operations/h)
100,000 operations min.
(at rated load and approx. 1,800 operations/h)
Section 5-3
Specifications
Specifications