Examples of Wiring for Each Application
8-2
Examples of Wiring for Each Application
8-2-1
Emergency Stop Switch Dual Channel Inputs with Manual Reset
Wiring
V
G
GND
Configuration
Parameter
group
Safety Input 0
0008
0009
0054
0055
Safety Input 1
0012
0013
Safety Input 11
0052
0053
0064
Test Output 0
0001
Test Output 1
0002
Test Output 2
0003
An example of the wiring and configuration when using the DST1-ID12SL-1 is
shown below.
IN0
IN1
T0
T1
E1
11
21
12
22
S1
Parameter name
Safety Input 0 Channel Mode
Safety Input 0 Test Source
Dual Channel Safety Input 0/1 Mode
Dual Channel Safety Input 0/1 Discrepancy Time
Safety Input 1 Channel Mode
Safety Input 1 Test Source
Safety Input 11 Channel Mode
Safety Input 11 Test Source
Dual Channel Safety Input 10/11 Mode
Test Output 0 Mode
Test Output 1 Mode
Test Output 2 Mode
IN
T2
E1: 24-V DC Power Supply (S8@@)
11
S1: Emergency Stop Switch (A165E or
A22E) (positive opening mechanism)
T1
G
S2: Reset switch
S2
Section 8-2
Value
Test pulse from test out
Test Output 0
Dual Channel Equivalent
100 x 10 ms
Test pulse from test out
Test Output 1
Used as standard input
Not Used
Single Channel
Pulse Test Output
Pulse Test Output
Power Supply Output
125