Mitsubishi Electric Q01UCPU User Manual page 81

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

Item
Execution of an input
contact instruction
Execution of an output
contact instruction
Execution of the OUT
instruction
(2) Response delay
An output response which corresponds to the status change in the input module delays for one scans (maximum)
depending on the on timing of an external contact.
[Example]
DX5
55
• DY5E turns on the earliest
Devices in the
CPU module
• DY5E turns on the latest
External contact
(External contact)
Devices in the
CPU module
DY5E
(External load)
The OR processing is performed with the input information of the input module (1)) and the input data of the
programming tool input area (2)) or remote input refresh area. The result is stored in the input (X) device memory
and is used as input data (3)) to execute the program.
Output data in the output (Y) device memory (4)) are read out and the program is executed.
The operation result of the program (5)) are output to the output module, and stored in the output (Y) device
memory.
0
OFF
External contact
DX5
OFF
(External
contact)
OFF
DY5E
(External
load)
0 55
56
END 0
ON
OFF
OFF
DX5
OFF
Delay time
(maximum 1 scan)
CHAPTER 2 APPLICATION OF PROGRAMMING
Description
A program that turns on the output
DY5E
DY5E when the input DX5 turns on.
55
56
ON
ON
ON
Delay time
55 56
: Input refresh
: Output refresh
ON
ON
2
79

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents