(4) Clearing latch data
(a) Data in the latch clear operation enable range (Latch (1) Start/End)
Perform either of the following.
• Remote latch clear
Perform the operation using a programming tool. (
• Latch clear by using the special relay and special register areas
1.
Change the operating status of the CPU module to STOP.
2.
Set "5A01
3.
Turn on SM339.
(b) Data in the latch clear operation disable range (Latch (2) Start/End) and in the file
register
Perform any of the following.
• Reset data by using the RST instruction.
• Transfer K0 by using the MOV or FMOV instruction. (
Instruction))
• Set parameters ("Clear Device's whole Memory" or "Clear all File Registers").
[Online]
Memory"/"Clear all File Registers"
Latching device data increases the scan time. When latching device data, consider the increase in scan time.
(
Page 473, Appendix 3.2 (6))
Note 2.2
Universal
Only the High-speed Universal model QCPU supports latch clear operation by using the special relay and special register
areas. Before executing the function, check the version of the CPU module used. (
" in SD339.
H
[PLC Memory Operation]
[Clear PLC Memory]
CHAPTER 2 APPLICATION OF PROGRAMMING
Page 135, Section 3.6.4)
Note 2.2
Note 2.2
MELSEC-Q/L Programming Manual (Common
"Clear Device's whole
Page 462, Appendix 2)