Mitsubishi Electric Q01UCPU User Manual page 422

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

(3) Local device setting
(a) Setting the local device range
In the Device tab of the PLC parameter dialog box, set the range that is used as a local device.
Note that the local device range is common to all programs, and cannot be changed for each program.
For example, if a local device range is specified as M0 to M100, this range setting applies to all programs that
use the local device.
M0
M100
● The 32-bit index modification range must not overlap with the local device setting range of the index register. If
overlapped, 32-bit index modification values will be written over the local device values.
● When CPU module parameters which contain local device setting of the index register are read from a programming tool
that does not support the setting, all of the index register data will be read out as global device data.
420
Program A
Program B
Local
device
Program C
Local
Local
device
device
Local device
range is
common to all
programs.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents