Appendix 5.4.2; Error Check Processing For Floating-Point Data Comparison Instructions; (Excluding High-Speed Universal Model Qcpu) - Mitsubishi Electric Q01UCPU User Manual

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

Appendix 5.4.2

(1) Input data check
Error check processing for floating-point data comparison instructions performed in the Universal model QCPU
are enhanced. Input of a "special value" (-0, nonnumeric, unnormalized number, or ±
special values are input, the CPU module detects "OPERATION ERROR" (error code: 4140).
When the LDE, ANDE, ORE, LDED, ANDED, and/or ORED instructions ( indicates one of the
following; =,<>,<,>,<=,>=) are used in the program, "OPERATION ERROR" (error code: 4140) may be detected if
invalid floating-point data exist. This occurs even when interlocks are provided using the valid data flags (the
signal which shows the floating-point validity).
Invalid floating-point data are not stored in the result of operations performed in the Universal model QCPU.
Those invalid data are considered to be stored in the following cases:
• The same device is used for storing floating-point data and other data, such as binary values, BCD values,
and strings.
 Use different devices for storing floating-point data and data other than floating-point data.
• Floating-point data externally written are invalid.
 Take measures on the external-source side so that valid data are written.
If an error occurs in the floating-point data comparison instructions, take appropriate measures to remove error
causes described above.
Ex.1)
Detecting "OPERATION ERROR" (error code: 4140) in the LDE instruction
[Ladder mode]
In the ladder block starting from the step 104, the floating-point data comparison instructions of the step 105 and
109 are not executed when the M101 (valid data flag) is off.
However, the LDE<= instruction of the step 105 and the ORE>= instruction of the step 109 are executed
regardless of the execution result of the LD instruction of the step 104 in the program above.
Therefore, even when the M101 is off, "OPERATION ERROR" (error code: 4140) will be detected in the LDE<=
instruction of the step 105 if a "special value" is stored in D100.
For the method of avoiding "OPERATION ERROR", refer to Page 537, Appendix 5.4.2 (2).
Error check processing for floating-point data
comparison instructions (excluding High-speed
Universal model QCPU)
APPENDICES