Mitsubishi Electric Q01UCPU User Manual page 57

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

(2) I/O assignment on a remote I/O stations
The devices of input (X) and output (Y) in the CPU module can be assigned to I/O modules and intelligent
function modules, which allows to control the modules in the remote I/O system such as CC-Link IE Field
Network, MELSECNET/H remote I/O network and CC-Link.
Also, the input (X) and output (Y) devices can be used as refresh-target devices for the link I/O (LX, LY) of CC-
Link IE Field Network master/local modules and MELSECNET/H modules.
CPU module
MELSECNET/H remote I/O network
(a) I/O numbers available on remote I/O stations
When the input (X) and output (Y) of the CPU module are used for the I/O numbers in the remote
station, assign the I/O numbers later than those used for the I/O modules and intelligent function
modules on the CPU module side.
When X/Y0 to X/Y3FF (1024 points) are used for the I/O modules and intelligent function modules on the
Ex.
CPU module side, X/Y400 and later can be used in the remote stations.
MELSECNET/H module
CC-Link module
Remote
station
X
0 to
Y
0 to
0 to
CHAPTER 2 APPLICATION OF PROGRAMMING
Remote
station
F: Input module
F: Output module
F: Intelligent function module
2
55