Mitsubishi Electric Q01UCPU User Manual page 126

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

(2) Operation when the operating status is changed from STOP to RUN
(a) Previous state (Default)
The CPU module outputs the output (Y) status immediately before changed to the STOP status and then
performs sequence program operations.
(b) Recalculate (output is 1 scan later)
All outputs are turned off.
The CPU module outputs the output (Y) status after sequence program operations are completed.
For the operation of the CPU module when the output (Y) status is forcibly turned on in the STOP status, refer
to Page 124, Section 3.4 (4).
(3) Setting the output mode when the operating status is changed from STOP to
RUN
Set the output mode when the operating status is changed from STOP to RUN in the PLC system tab
of the PLC parameter dialog box.
(4) Precautions
The following tables shows the output status of the CPU module when the operating status is changed from
STOP to RUN after the outputs (Y) are forcibly turned on in the STOP status.
Output mode ("Output Mode at
STOP to RUN") selected
Previous State
Recalculate (Output is 1 scan later)
124
Operating status change (STOP to RUN)
Is "Previous state" set?
YES ("Previous state" is set.)
The output (Y) status immediately before
changed to the STOP status is output.
Sequence program operations
are performed.
Select either of
these.
NO ("Recalculate (output is 1 scan later)" is set.)
The output status prior to STOP is output. The on status is not held if the output
status prior to STOP was off.
The on status is held and output.
Output status