(5) Checking/disabling executional conditioned device test settings
For how to check/disable executional conditioned device test settings, refer to the following.
Operating manual for the programming tool used
(a) Usage of the executional conditioned device test
Usage of the executional conditioned device test can be checked in the special register (SD840).
(b) Number of settings that can be disabled simultaneously in one scan
Eight executional conditioned device test settings can be disabled simultaneously in one scan. When nine or
more executional conditioned device test settings are to be disabled simultaneously, they will be disabled over
multiple scans.
(6) Batch-disabling executional conditioned device test settings
For how to batch-disable executional conditioned device test settings, refer to the following.
Operating manual for the programming tool used
(7) Cases where executional conditioned device test settings cannot be registered
or disabled
In the following cases, executional conditioned device test setting cannot be registered or disabled.
When multiple settings are to be registered, no setting can be registered if any of the settings applies to the cases
below.
(a) Executional conditioned device test settings cannot be registered
• Specified program does not exist.
• Specified step does not exist.
• Specified device does not exist.
• The number of registered executional conditioned device test settings exceeds 32.
(b) Executional conditioned device test settings cannot be disabled
• Specified program does not exist.
• Specified step does not exist.
• Specified device does not exist.
• No executional conditioned device test setting has been registered.
162