Mitsubishi Electric Q01UCPU User Manual page 174

Hide thumbs Also See for Q01UCPU:
Table of Contents

Advertisement

(3) Instructions that do not operate normally during online change
When data are written to the CPU module in the RUN status, the following instructions do not operate normally.
• Rise instruction
• SCJ instruction
• STMR instruction
(a) Rise instruction
The rise instruction is not executed when the instruction is in the data written to the CPU module in the RUN
status, even if the execution condition (off
OFF
The corresponding rise instructions are PLS and P.
172
Completion of
online change
A
END
0
X0 status
ON
X0
OFF
OFF
ON
M0
OFF
ON
X0
OFF
ON
ON
ON
M0
OFF
ON
X0
OFF
OFF
ON
ON
M0
OFF
on) is met.
X0
[ PLS M0 ]
A
END
0
END
0
1 scan
The rise instruction is not executed even
if the execution condition is off
on.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents