Parameter
Item
No.
1005
Common Pointer No.
Points Occupied by
1007
Empty Slot
Fixed Scan
1008
Interval (n:
System
28 to 31)
Interrupt
Settings
High Speed
100F
Interrupt
to 1012
Setting
Interrupt Program/Fixed
1008
Scan Program Setting
Service Processing
1013
Setting
PLC Module Change
1017
Setting (PLC Module
Change Setting)
Description
Set the start number of common
H
pointers.
Set the number of points for
empty slots on the
H
main/extension base units.
Set each execution interval for
H
the interrupt pointers (I28 to I31).
Set this parameter when a high-
H
speed interrupt pointer (I49) is
H
used.
Enable or disable high speed
execution of interrupt programs
H
or fixed scan programs.
Select any of the following
options.
• Execute the process as the
scan time proceeds.
• Specify service process time.
H
• Specify service process
execution counts.
• Execute it while waiting for
constant scan setting.
Set items required when
performing the CPU module
H
change with memory card
function.
Setting range
P0 to 4095
0, 16, 32, 64, 128, 256, 512, or 1024
Points
0.5ms to 1000ms
(in increments of 0.5ms)
-
Selected/deselected
• 1 to 99% (in increments of 1%)
• 1 to 10 (in increments of 1 time)
• 0.2 to 1000ms (in increments of
0.1ms)
• Blank
• Backup Start Setup Contact
• Backup Start Contact
• Backup Target Data
• Title Setting
APPENDICES
Default
Reference
Page 407,
Blank
Section
4.10.2
Page 52,
16 Points
Section 2.2.2
• I28: 100.0ms
• I29: 40.0ms
Page 408,
• I30: 20.0ms
Section 4.11
• I31: 10.0ms
Page 222,
-
Section 3.21
Page 80,
Section 2.9,
Deselected
Page 96,
Section
2.10.4
Execute the
Page 238,
process as the
Section
scan time
3.24.1
proceeds.: 10%
Page 257,
Blank
Section 3.31