AC Power Connections

Terminals with an integrated AC power supply have these power ratings.
Table 40 - AC Power Ratings
Terminal
Input Voltage
400, 600
100...240V AC (50...60 Hz)
700, 1000, 1250, 1500 100...240V AC (50...60 Hz)
Protective Earth and Functional Earth Connections
PanelView Plus 6 devices with an AC power input have a protective earth
terminal you must connect to a low-impedance earth ground. The protective
earth terminal is on the power input terminal block.
In addition to the protective earth connection, the 700 and 1500 terminals also
IMPORTANT
have a functional earth terminal that you must connect to a low-impedance
earth ground. The functional earth connection is on the back of the display.
ATTENTION: The protective earth and functional earth connections to ground
are mandatory.
• The functional earth is required for Electromagnetic compliance (EMC) with the
European Union (EU) EMC directive for CE-mark conformance.
• The protective earth is required for both safety and regulatory compliance.
Table 41 - Protective Earth/Functional Earth Wire Specifications for AC Power
Earth Connections
Protective earth
400, 600
Protective earth
700 to 1500
Functional earth
GND
700 to 1500 only
Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017
Power Consumption
35VA max
160VA max
Wire Type
Stranded or solid
Cu 90 °C (194 °F)
Stranded or solid
Cu 90 °C (194 °F)
Stranded or solid
Cu 90 °C (194 °F)
Install Terminal
Chapter 2
Terminal Screw
Wire Gauge
Torque
2
2.1...3.3 mm
0.45...0.56 N•m
(14...12 AWG)
(4...5 lb•in)
2
2.1...3.3 mm
0.56 ...0.90 N•m
(14...12 AWG)
(5...8 lb•in)
2
2.1...5.3 mm
1.13... 1.36 N•m
(14...10 AWG)
(10...12 lb•in)
41