Controller Connections

Table 74 - PanelView Plus 6 Terminals to SLC Controllers
Protocol
PanelView Plus 6 Comm Port
RS-232 (DF1) port (9-pin)
DF1
All terminals
RS-232 (DH-485) port (9-pin)
All terminals
DH-485
DH-485 port
700 to 1500 terminals only
Require 2711P-RN6, 2711P-RN6K
EtherNet/IP port
All terminals
EtherNet/IP
2711P-RN20 provides additional port - 700 to
1500 terminals only
ControlNet
ControlNet port
700 to 1500 terminals only
Require 2711P-RN15S, 2711P-RN15SK
DH+ port
DH+
700 to 1500 terminals only
Require 2711P-RN6, 2711P-RN6K
Table 75 - PanelView Plus 6 Terminals to PLC-5 and MicroLogix Controllers
Protocol
PanelView Plus 6 Comm Port
RS-232 (DF1) port (9-pin)
DF1
All terminals
RS-232 (DH-485) port (9-pin)
All terminals
DH-485
DH-485 port
700 to 1500 terminals only
Require 2711P-RN6, 2711P-RN6K
EtherNet/IP port
All terminals
EtherNet/IP
2711P-RN20 provides additional port - 700
to 1500 terminals only
ControlNet port
ControlNet
700 to 1500 terminals only
Require 2711P-RN15S, 2711P-RN15SK
DH+ port
DH+
700 to 1500 terminals only
Require 2711P-RN6, 2711P-RN6K
(1) The AIC+ module is recommended for isolation purposes when the terminal and controller are not on same power supply.
The tables provide a summary of PanelView Plus 6 connections to controllers
and interface modules for runtime communication.
SLC 500, 5/01, 5/02
SLC 5/03, 5/04, 5/05
CH1 RJ45
CH0 (9-pin RS-232)
(DH-485)
(DF1 or DH-485)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
Use AIC+ module
2711-NC13 (5 m/16 ft)
(1761-NET-AIC) to connect to
2711-NC14 (10 m/32 ft)
port 1 or 2
1761-CBL-AS03
Use AIC+ module
(3 m/10 ft)
(1761-NET-AIC)
1761-CBL-AS09
to connect to port 3
(9 m/30 ft)
Use 1761-NET-ENI module
with Ethernet cable
PLC-5, PLC-5C, PLC-5E
MicroLogix 1400, 1500LRP
CH0 (25-pin RS-232)
CH1/CH2 (9-pin RS-232)
(DF1)
(DF1 or DH-485)
2711-NC13 (5 m/16 ft)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2711-NC14 (10 m/32 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
To PLC-5E with
1585J-M type cable or
2711P- CBL-EX04 (4 m/14 ft)
To PLC-5C with
ControlNet cable
Shielded twinaxial cable
(1770-CD)
Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017
SLC 5/03
CH1 (RJ45)
(DH-485)
Use AIC+ module
(1761-NET-AIC) to
connect to port 1 or 2
1761-CBL-AS03
(3 m/10 ft)
1761-CBL-AS09
(9 m/30 ft)
MicroLogix 1000, 1100, 1200,
1400, 1500LSP
CH0 (8-pin Mini DIN)
(DF1 or DH-485)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
Use AIC+ module
(1761-NET-AIC)
to connect to port 3
Use 1761-NET-ENI module
with Ethernet cable
Terminal Connections
Chapter 6
SLC 5/04
SLC 5/05
CH1 (DH+)
CH1 (ENET)
1585J-M type cable or
2711P-CBL-EX04
(4 m/14 ft)
Shielded
twinaxial
cable (1770-CD)
MicroLogix 1100, 1400
Ethernet
(1)
1585J-M type cable or
(1)
2711P- CBL-EX04 (4 m/14 ft)
153