Chapter 2
Install Terminal

DC Power Connections

38
700 to 1500 Terminals
Follow these steps to remove the terminal block from a 700 to 1500 terminal.
1. Loosen the two screws that secure the terminal block.
2. Gently pull the terminal block away from the connector.
Two-position
DC Terminal Block
Follow these steps to install the terminal block.
1. Reattach the terminal block to the connector until seated.
2. Tighten the two screws that secure the terminal block to a torque of
0.40...0.51 N•m (3.5...4.5 lb•in).
Terminals with an integrated 24V DC power supply have these power ratings.
Table 37 - DC Power Ratings
Terminal
Power Supply
400, 600
Nonisolated
700 to 1500
Isolated
The power supply is internally protected against reverse polarity. Connecting
DC+ or DC- to the earth/ground terminal can damage the device.
ATTENTION: Applying an AC power source to a terminal with a DC power input
can damage the device.
External Power Supply
Use a dedicated 24V DC, safety extra-low voltage (SELV) or protective
extra-low voltage (PELV) power supply to power each PanelView Plus 6 device.
ATTENTION: Use a SELV or PELV power supply as required by local wiring codes
for your installation. These power supplies provide protection so that under
normal and single fault conditions, the voltage between conductors and earth
ground does not exceed a safe value.
Terminals with an isolated DC power supply can be powered by the same
TIP
power source as other equipment, such as a DC power bus.
Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017
Three-position
AC Terminal Block
Input Voltage
24V DC nom (18...30V DC)
24V DC nom (18...32V DC)
Power Consumption
15 W max (0.6 A at 24V DC)
70 W max (2.9 A at 24V DC)