Wiring and grounding guidelines

Advertisement

Technical Data
Wiring and Grounding Guidelines
for PanelView Plus Terminals
Catalog Number 2711P
About This Publication
Topic
Important User Information
Terms and Definitions
Wiring and Safety Guidelines
Hazardous Location Advisory
Remove and Install the Power Terminal Block
PanelView Plus Nonisolated DC Terminals
PanelView Plus Isolated DC Terminals
PanelView Plus AC Terminals
Communication Port Isolation
Ethernet Cable
Guidelines for Powering Nonisolated DC PanelView Plus Terminals
Guidelines for Powering the Isolated DC PanelView Plus Terminals
How to Avoid Grounding Problems
Additional Resources
This document provides information on how to properly wire, ground, and apply
power to these devices:
• PanelView Plus 6 terminals (700 to 1500)
• PanelView Plus 700 to 1500 terminals supporting FactoryTalk View
Machine Edition software, version 5.1 or earlier
• PanelView Plus 400 and 600 terminals
• PanelView Plus Compact terminals (400, 600, 1000)
Throughout this publication, PanelView Plus terminals is used generically to
refer to all terminals unless specifically stated.
Page
2
3
4
4
5
7
12
17
21
22
23
26
27
33

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley 2711P

  • Page 1 Technical Data Wiring and Grounding Guidelines for PanelView Plus Terminals Catalog Number 2711P Topic Page Important User Information Terms and Definitions Wiring and Safety Guidelines Hazardous Location Advisory Remove and Install the Power Terminal Block PanelView Plus Nonisolated DC Terminals...
  • Page 2: Important User Information

    Identifies information that is critical for successful application and understanding of the product. IMPORTANT Allen-Bradley, DH+, FactoryTalk View Machine Edition, PanelView Plus, PanelView Plus Compact, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
  • Page 3: Terms And Definitions

    In typical industrial systems, the ground bus is mounted on the back panel of the enclosure. The protective earth and functional earth terminals of the various equipment in the enclosure are connected to the ground bus bar. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 4: Wiring And Safety Guidelines

    Do not connect or disconnect components unless power has been switched off. All wiring must comply with N.E.C. articles 501, 502, 503, and C.E.C. section 18-1J2, as appropriate. Peripheral equipment must be suitable for the location it is used in. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 5: Remove And Install The Power Terminal Block

    1. Press the terminal block base in first with the block leaning outward. 2. Gently push the top of the terminal block back to the vertical position to snap in the locking tab. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 6 3-position AC or DC Follow these steps to install the terminal block. 1. Reattach the terminal block to the connector until seated. 2. Tighten the two screws that secure the terminal block to the connector. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 7: Panelview Plus Nonisolated Dc Terminals

    CE logic module with 256 MB nonvolatile memory and RAM (1) These logic modules support FactoryTalk View Machine Edition software, version 5.1 or earlier. Refer to Communication Port Isolation on page 21 for information on IMPORTANT communication port isolation. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 8 Wiring and Grounding Guidelines for PanelView Plus Terminals External Power Supply for Nonisolated DC Terminals Use a single, 24V DC power supply, such as catalog number 2711P-RSACDIN, to power PanelView Plus terminals with a nonisolated DC power supply. Using a separate, isolated, and ungrounded source with each terminal prevents ground loop currents from damaging the product.
  • Page 9 Use the shortest, practical wire length to connect the functional earth/ground to a low-impedance earth/ground. The ground wire must be either green or green with a yellow stripe. Refer to local wiring codes and regulations for grounding requirements. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 10 Figure 3 - Functional Earth Connection for 400 and 600 DC Terminals Ground Bus Tapped Hole Star Washer DC + Functional Earth Ground Lug DC - Bolt Enclosure Wall Ground Bus To Grounding Electrode System Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 11 AC power source requires an AC-to-DC power supply with a UL Class 2 or SELV output, or the 2711P-RSACDIN power supply. Catalog number 2711P-RSACDIN is a UL accepted power supply for the PanelView Plus terminals. The power supply converts AC power to DC power, provides a SELV output, and has electrical input ratings of 85…264V AC...
  • Page 12: Panelview Plus Isolated Dc Terminals

    External Power Supply for Isolated DC Terminals Use a SELV or PELV, 24V DC power supply, such as catalog number 2711P-RSACDIN, to power a PanelView Plus 700 to 1500 terminal with an isolated DC logic module The isolated DC terminals may be powered by the same power source as other equipment, a DC power bus.
  • Page 13 Figure 5 - Earth/Ground Connection for 700 to 1500 Isolated DC Terminals Ground Bus Earth/Ground to Ground Bus Enclosure Wall Tapped Hole Star Washer Ground Lug To Grounding Electrode System Ground Bus Bolt Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 14 AC power source requires an AC-to-DC power supply with a SELV output, or the 2711P-RSACDIN power supply. Catalog number 2711P-RSACDIN is a UL accepted power supply for the PanelView Plus terminals. The power supply converts AC power to DC power, provides a SELV output, and has electrical input ratings of 85…264V AC...
  • Page 15: Connect Panelview Plus Dc Terminals To Dc Power

    • On the 400 and 600 terminals, secure the earth/ground wire to the functional earth/ground terminal on the input power terminal block. • On the 700 to 1500 terminals, secure the earth/ground wire to the earth/ground terminal screw at the bottom of the display. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 16: Using Isolated Dc Logic Modules In Marine Applications

    Use Corcom 6VW1 or equivalent filter type. PanelView Plus Terminal With a Marine-certified Logic Module DC- DC+ Earth/Ground 1 m (39 in.) maximum GND to Ground Bus Line Filter Earth/Ground GND to Ground Bus Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 17: Panelview Plus Ac Terminals

    Marine-certified logic module with 256 MB nonvolatile memory and RAM 2711P-RP7A Marine-certified CE logic module with 256 MB nonvolatile memory and RAM (1) These logic modules support FactoryTalk View ME software, version 5.1 or earlier. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 18 Figure 8 - Protective Earth Connection for 400 and 600 AC Terminals Protective Earth to Ground Bus L2/Neutral Tapped Hole Enclosure Wall Star Washer Ground Bus Ground Lug Bolt To Grounding Electrode System Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 19 Figure 9 - Protective Earth and Functional Earth Connection for 700 to 1500 AC Terminals L1 L2N Protective Earth L2/Neutral to Ground Bus Functional Earth to Ground Bus Tapped Hole Ground Bus Star Washer Enclosure Wall Ground Lug Bolt To Grounding Electrode System Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 20: Connect To Ac Power

    PanelView Plus 6 (700 to 1500) Terminals PanelView Plus 400 and 600 Terminals Other PanelView Plus 700 to 1500 Terminals Look Similar L2/Neutral L2/Neutral Protective Earth Protective Earth Functional Earth/Ground to Bus to Ground Bus to Ground Bus Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 21: Communication Port Isolation

    Isolation DH-485 2711P-RN6, 2711P-RN6K Isolated 2711P-RN6, 2711P-RN6K Isolated Remote I/O 2711P-RN6 Isolated DeviceNet 2711P-RN10H Isolated ControlNet 2711P-RN15S, 2711P-RN15SK Isolated (1) Remote I/O and DeviceNet networks are supported but no longer available for order. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 22: Ethernet Cable

    An electrical arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 23: Guidelines For Powering Nonisolated Dc Panelview Plus Terminals

    UL Class 2 power source for UL installations. The supply you choose depends on the regulatory agency that is applicable to the installation. The 2711P-RSACDIN power supply is approved for use with PanelView Plus terminals in most installations.
  • Page 24: Power The Nonisolated Dc Panelview Plus Terminals

    DC- wiring. Figure 12 - Separate AC Power Supplies to Power Multiple DC Terminals AC/DC Power Supply AC/DC Power Supply 2711P-RSACDIN 2711P-RSACDIN Circuitry Circuitry PanelView Plus PanelView Plus Terminal Terminal Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 25: Use A Single Point Ground

    Apply Correct Input Voltage ATTENTION: Apply the correct voltage type to the DC power terminal block. Do not connect an AC power source to the DC power terminal block. This will damage the PanelView Plus terminal. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 26: Guidelines For Powering The Isolated Dc Panelview Plus Terminals

    Apply Correct Input Voltage Apply the correct voltage type to the DC power terminal block. ATTENTION: Do not connect an AC power source to the DC power terminal block. This will damage the PanelView Plus terminal. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 27: Multiple Ground Connections

    A ground loop occurs in a system with parallel ground paths. A ground loop can cause excessive current to flow in the PanelView Plus terminal. Excessive current flow can damage the PanelView Plus terminal. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 28 The power supply of the isolated DC PanelView Plus 700 to 1500 terminals lets you power multiple terminals from one DC power source without creating a ground loop. DC Power Supply +24V DC Power Common Circuitry Circuitry Isolated Isolated PanelView Plus PanelView Plus Terminal Terminal Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 29: High Current From Multiple Ground Connections

    Power Power > > Common Common Common DC Motor DC Motor > Circuitry Circuitry PanelView Plus PanelView Plus Motor Common Motor Common Terminal Terminal Tied to Earth tied to Earth > > > Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 30 DC equipment, powered by a single DC power source. Single Power Supply with Isolated DC Terminal AC/DC Power Supply +24V DC Power Common DC Motor, Solenoid Circuitry Isolated Common Tied PanelView Plus Terminal to Earth Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 31: Ground Shift Problem

    Equipment Comms Port Terminal Comms Comms Circuitry Circuitry Comms Circuitry > > > Circuitry > > Isolated Motor Noise PanelView Plus Motor Noise Communication Lightning, Nonisolated Lightning, Ground Shift Comms Port Ground Shift Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 32: Ground Reference Problem

    DC - DC + Comms Comms Circuitry Circuitry Circuitry Circuitry Comms > > > > > PanelView Plus Communication Equipment Isolated PanelView Plus Communication Equipment Nonisolated Nonisolated Comms Port Communication Terminal Comms Port Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 33: Additional Resources

    PanelView Plus terminals. You can view or download publications and translated versions of the installation instructions at http://www.rockwellautomation.com/literature. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative. Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011...
  • Page 36: Rockwell Automation Support

    Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 2711P-TD001D-EN-P - February 2011 Supersedes Publication 2711P-TD001C-EN-P - September 2008 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.