Upgrade Terminal Firmware Over The Network - Allen-Bradley PanelView Plus 6 User Manual

Hide thumbs Also See for PanelView Plus 6:
Table of Contents

Advertisement

Chapter 7
Firmware Upgrades
Upgrade Terminal Firmware
over the Network
Follow these steps to copy firmware files to the terminal over a network by using RSLinx Enterprise software and Ethernet
communication.
1. Run the Firmware Upgrade Wizard:
• In FactoryTalk View Studio software, from the Tools menu, choose Firmware Upgrade Wizard.
• Choose Start>Programs>Rockwell
Software>FactoryTalk
View>Tools>ME Firmware Upgrade
Wizard.
2. Click Upgrade firmware on terminal
and click Next.
3. Click Yes to continue.
It is not necessary to back up files
on PanelView Plus 6 terminals.
4. Click Network Connection
(using RSLinx Enterprise) and
click Next.
This is the only valid selection
for PanelView Plus 6 terminals.
160
You can upgrade firmware in a terminal connected to a computer over a direct
network connection. The network connection requires a computer running the
Firmware Upgrade Wizard (FUW) and RSLinx Enterprise software, version 5.0
or later.
RSLinx Enterprise software is required so that you can select the terminal on the
network.
Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents