Wiring a connector

This section describes how to wire connectors for external devices.
Applicable connectors
The following reference products are the connector types and crimping tool for a module.
■ 40-pin connectors
Type
Soldering type connector (straight type)
Crimping type connector (straight type)
Soldering type connector (dual purpose (straight/oblique) type)
■ 40-pin connector crimping tool
Manufacturer
FUJITSU COMPONENT LIMITED
For how to wire the connector and how to use the crimping tool, contact the manufacturer.
Wiring method
■ A6CON1, A6CON4
(1)
5 INSTALLATION AND WIRING
128
5.7 Wiring
Type
Crimping tool
Model
Applicable wire size
A6CON1
0.088 to 0.3 (28 to 22 AWG) (stranded wire)
A6CON2
0.088 to 0.24 (28 to 24 AWG) (stranded wire)
A6CON4
0.088 to 0.3 (28 to 22 AWG) (stranded wire)
Model
FCN-363T-T005/H
1.
Loosen the four fixing screws on the connector and
remove the screws. Open the connector cover from the
connector side.
2.
Solder the wires and coat them with heat shrinkable
tubes (1).
3.
Check the terminal layout and wire them to the
connector. When the connector is plugged into an I/O
module, an FG wire needs not to be installed.
Contact
www.fujitsu.com/jp/group/fcl/en/