■ Engineering tool
• The version of an engineering tool that supports the MELSECNET/H network module is restricted. ( MELSEC iQ-R
CPU Module User's Manual (Application))
• When the module occupying two slots (QJ71LP21S-25) is mounted, it is displayed on an engineering tool as occupying one
slot. Therefore, when setting the module on "Module Configuration", mount the blank cover module (QG60) on the left side
of the QJ71LP21S-25 mounted slot to secure an empty space of one slot (16 points). Then, set the empty space of one slot
(16 points) in "I/O Assignment Setting" in the [I/O Assignment] tab on the "System Parameter" window.
(2) (1)
• Data communications from the engineering tool (GX Works3) to other stations (stations where the engineering tool is not
connected) cannot be performed via MELSECNET/H.
• On the system monitor and MELSECNET diagnostics of the engineering tool (GX Works3), the mode of the MELSECNET/
H network module is always displayed as "Online".
• None of T, C, and ST can be specified for the device set in the link refresh settings. Specify another device.
• There are precautions for MELSECNET diagnostics of the engineering tool (GX Works3) via following devices.
Device
CC-Link IE Controller Network interface board
CC-Link IE Field Network interface board
GOT
■ GX works2 and GX Developer
• From GX Works2 connected to a MELSEC iQ-R series CPU module, access to a MELSEC-Q series or MELSEC-L series
CPU module is possible via the MELSECNET/H network module mounted on the RQ extension base unit. For the access
via a MELSEC iQ-R series CPU module, use GX Works2 with the version of 1.519R or later.
• For data access from GX Works2 to other stations via a MELSEC iQ-R series CPU module, a remote password, if it is set,
cannot be canceled from GX Works2. Cancel the password using the engineering tool that supports a MELSEC iQ-R series
CPU module.
• From GX Developer, access to other stations via a MELSEC iQ-R series CPU module is not possible.
APPX
170
Appendix 5 How to Use MELSEC-Q Series Modules
(1) QJ71LP21S-25 (module occupying two slots)
(2) QG60 (blank cover module)
Precaution
Use the SW1DNC-MNETG-B with version 1.22Y or later and the ROM with version 2T or
later.
Use the SW1DNC-CCIEF-B with version 1.10L or later.
MELSECNET diagnostics cannot be used If the engineering tool (GX Works3) is
connected to the programmable controller using the FA transparent function of GOT (in a
CC-Link IE Controller Network or a CC-Link IE Field Network connection).