Periodic Inspection - Mitsubishi Electric MELSEC iQ-R Series Configuration Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

6.2

Periodic Inspection

This section describes items that must be inspected one or two times every six months to one year.
When the equipment has been relocated or modified, or wiring layout has been changed, inspect the items.
Item
Inspection Item
1
Environment
2
Power supply voltage check
3
Installation
4
Connection status
5
Battery
6
Module diagnostics
7
Maximum scan time
*1 The temperature in the control panel installed a programmable controller is called the ambient temperature.
*2 When an extended temperature range base unit is used, each module can be used in the environment of 0 to 60.
6 MAINTENANCE AND INSPECTION
142
6.2 Periodic Inspection
Inspection method
*1
Ambient temperature
Measure the temperature by
using a thermometer.
Ambient humidity
Measure the humidity by using
a hygrometer.
Atmosphere
Measure corrosive gases.
Measure a voltage between the
terminals of 100/200VAC and
24VDC.
Looseness and rattling
Touch the module to check for
the looseness and rattling.
Attachment of dirt and
Check visually.
foreign matter
Terminal screw
Check for the terminal screw
loosening
loosening.
Clearance between the
Check visually.
solderless terminals
Connector loosening
Check visually.
Check the BATTERY LED on
the CPU module.
Check the length of term after
purchasing the battery.
Check that SM51 or SM52 is
turned off using a engineering
tool.
Check an event history using
the module diagnostics.
Check the values of SD526
and SD527 using a
engineering tool.
Judgment criteria
*2
0 to 55
5 to 95%RH
No corrosive gases
85 to 264VAC
15.6 to 31.2VDC
The module must be mounted
securely.
Dirt and foreign matter must
not be attached.
The terminal screws must not
be loose.
The proper clearance must be
provided between solderless
terminals.
The cable connector must not
be loose.
The LED must be off.
The battery must not be used
more than five years.
SM51 or SM52 must be off.
An event history must not be
updated.
Maximum scan time must be
within the allowable range
given in the specification of the
system.
Corrective action
Create the environment that
satisfies the judgment criteria
Change the supply power.
Retighten the screws.
If the module is loose, fix the
module with screws.
Remove them. Clean the
programmable controller.
Retighten the screws.
Provide the proper clearance.
Connect the connector with no
loosening securely.
Replace the battery when the
LED is on.
Replace the battery if it has
been used more than 5 years.
Replace the battery when
SM51 or SM52 is on.
 GX Works3 Operating
Manual
Specify causes that increase
the scan time.
Check the operation status of
the trigger signal that passes
through a loop if loop positions
exist in the sequence program.