Mitsubishi Electric MELSEC iQ-R Series Configuration Manual page 183

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• Use the FG terminals of the CC-Link module and CC-Link stations as shown below to connect to the FG line inside the
control panel.
(Blue)
DA
Terminating
resistor
(White)
DB
(Yellow)
DG
Ver.1.10-compatible
SLD
CC-Link dedicated cable
FG
• Use a CE-marked power supply to which the module power supply or external power supply is connected. Ground the FG
terminals.
• Keep each power cable connected to the external power supply terminal or module power supply terminal to 30m or less.
• Connect a noise filter to the external power supply Use a noise filter with the damping characteristic, MA1206
(manufactured by TDK-Lambda Corporation) or equivalent. Note that a noise filter is not required if the module is used in
Zone A defined in EN61131-2.
Manufacturer
TDK-Lambda Corporation
• Keep the length of signal cables connected to the analog input terminals of the AJ65BT-64RD3, AJ65BT-64RD4, and
AJ65BT-68TD to 30m or less. Wire cables connected to the external power supply and module power supply terminal in the
control panel where the module is installed.
• For the cable connected to the power supply terminal or the AJ65SBT-RPS, AJ65SBT-RPG, or AJ65BT-68TD, install a
ferrite core with the damping characteristics, ZCAT3035-1330 (manufactured by TDK Corporation) or equivalent. Wrap the
cable around the ferrite core by one as shown below.
Manufacturer
TDK Corporation
• To supply the module power supply terminal of the AJ65BTB2-16R/16DR, or AJ65SBTB2N-8A/8R/8S/16A/16R/16S with
power using the AC/DC power supply, follow as shown below.
• Install the AC/DC power supply in the control panel where the module is installed.
• Use a reinforced or double insulated CE-marked AC/DC power supply, and ground the FG terminal. (AC/DC power supply used for the tests conducted by
Mitsubishi: DLP-120-24-1 (manufactured by TDK-Lambda Corporation))
• For the cable connected to the AC input terminal and DC output terminals of the AC/DC power supply, attach a ferrite core. Wrap the cable around the ferrite
core by one as shown below. (Ferrite core used for the tests conducted by Mitsubishi: ESD-SR-250 (manufactured by NEC TOKIN Corporation))
(Blue)
(Blue)
DA
(White)
(White)
DB
(Yellow)
(Yellow)
DG
Ver.1.10-compatible
SLD
CC-Link dedicated cable
FG
Contact
www.tdk-lambda.com
Contact
www.global.tdk.com
(Blue)
DA
Terminating
resistor
(White)
DB
(Yellow)
DG
SLD
FG
Appendix 6 EMC and Low Voltage Directives
A
APPX
181