Chapter 4 Specifications; General Specifications - Mitsubishi Electric MELSEC iQ-R Series Configuration Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

4
SPECIFICATIONS
4.1

General Specifications

This chapter describes the general specifications of the modules used.
Item
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Shock resistance
Operating atmosphere
*1
Operating altitude
Installation location
*2
Overvoltage category
*3
Pollution degree
Equipment class
*1 Do not use or store the programmable controller under pressure higher than the atmospheric pressure of altitude 0m. Doing so may
cause malfunction. When using the programmable controller under pressure, please consult your local Mitsubishi representative.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power
distribution network and the machinery within premises. Category  applies to equipment for which electrical power is supplied from
fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must be expected
occasionally.
*4 Use the special coated products which comply with the IEC 60721-3-3 3C2 in the environment with the corrosive gases. For details on
the special coated products, please consult your local Mitsubishi representative.
*5 When the programmable controller is used at altitude above 2000m, the withstand voltage performance and the upper limit of the
operating ambient temperature decrease. Please consult your local Mitsubishi representative.
*6 All modules mounted on the extended temperature range base unit provide the same performance as the modules used in an operating
ambient temperature of 0 to 55, even though they are used in an operating ambient temperature of 0 to 60. When using the
modules in the environment of the temperature exceeding 60, please consult your local Mitsubishi representative.
4 SPECIFICATIONS
84
4.1 General Specifications
Specifications
0 to 55 (When an extended temperature range base unit is not used)
*6
0 to 60
(When an extended temperature range base unit is used)
-25 to 75
5 to 95%RH, non-condensing
5 to 95%RH, non-condensing
Compliant with
JIS B 3502 and
IEC 61131-2
Under
intermittent
vibration
Under
continuous
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147m/, 3 times each in X, Y, and Z bidirections)
*4
No corrosive gases
, flammable gases, less conductive dust
*5
0 to 2000m
Inside a control panel
 or less
2 or less
Class 
Frequency
Constant
acceleration
5 to 8.4Hz
8.4 to 150Hz
9.8m/
5 to 8.4Hz
8.4 to 150Hz
4.9m/
Half amplitude
Sweep count
3.5mm
10 times each in
X, Y, and Z
directions
1.75mm

Advertisement