Number
Effect/cause
140016
The hardware does not support the configured
interrupt.
140017
The set interrupt is in use by another driver.
140018
The consistency check was disabled by SIMOTION
Scout. Only a corresponding note appears.
140019
SIMOTION Scout is downloading a new project to
the controller. Connection to the controller is
canceled.
140020
The version in the controller and that of the project
(FWX file) do not match.
Connection to the controller is canceled
150000
No more data is read or written. Possible causes:
The cable is defective.
The PLC does not respond, is defective, etc.
The wrong port is used for the connection.
System overload.
150001
Connection is up because the cause of the
interruption has been eliminated.
160000
No more data is read or written. Possible causes:
The cable is defective.
The PLC does not respond, is defective, etc.
The wrong port is used for the connection.
System overload.
160001
Connection is up because the cause of the
interruption has been eliminated.
160010
No connection to the server because the server
identification (CLS-ID) cannot be determined.
Values cannot be read or written.
160011
No connection to the server because the server
identification (CLS-ID) cannot be determined.
Values cannot be read or written.
160012
No connection to the server because the server
identification (CLS-ID) cannot be determined.
Values cannot be read or written.
160013
The specified server was started as InProc server.
This has not been released and may possibly lead
to incorrect behavior because the server is running
in the same process area as the WinCC flexible
Runtime software.
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
Remedy
Change the interrupt number.
Change the interrupt number.
Enable the consistency check with SIMOTION Scout and
once again download the project to the PLC.
Wait until the end of the reconfiguration.
The following remedies are available:
Download the current version to the PLC using
SIMOTION Scout.
Regenerate the project using WinCC flexible ES, close
WinCC flexible Runtime and restart with a new
configuration.
Ensure that the cable is plugged in, the controller is
operational, the correct interface is being used.
Restart the system if the system alarm persists.
-
Ensure that the cable is plugged in, the controller is
operational, the correct interface is being used.
Restart the system if the system alarm persists.
-
Check access rights.
Check, for example, if
the server name is correct
the computer name is correct
the server is registered
Check, for example, if
the server name is correct
the computer name is correct
the server is registered
Note for advanced users:
Interpret the value from HRESULT.
Configure the server as OutProc Server or Local Server.
Appendix
A.2 System alarms