A.2 System alarms
Number
Effect/cause
290054
Message reporting that the import of data records
was completed.
290055
Message reporting that the import of data records
was canceled due to an error.
290056
Error when reading/writing the value in the
specified line/column.
The action was canceled.
290057
The tags of the recipe specified were toggled from
"offline" to "online" mode.
Each change of a tag in this recipe is now
immediately downloaded to the controller.
290058
The tags of the specified recipe were toggled from
"offline" to "online" mode.
Modifications to tags in this recipe are no longer
immediately transferred to the controller but must
be transferred there explicitly by downloading a
data record.
290059
Message reporting that the specified data record
was saved.
290060
Message reporting that the specified data record
memory was cleared.
290061
Message reporting that clearing of data record
memory was canceled due to an error.
290062
The data record number is above the maximum of
65536.
This data record cannot be created.
290063
This occurs with the system function
"ExportDataRecords" when the parameter
"Overwrite" is set to No.
An attempt has been made to save a recipe under
a file name which already exists.
The export is canceled.
290068
Request to confirm if all data records in the recipe
should be deleted.
290069
Request to confirm if all data records of all recipes
should really be deleted.
290070
The data record specified is not in the import file.
290071
During the editing of data record values, a value
was entered which exceeded the low limit of the
recipe tag.
The entry is discarded.
290072
When editing data record values, a value was
entered which exceeds the high limit of the recipe
tag.
The entry is discarded.
172
Remedy
-
Ensure that the structure of the data records at the
storage location and the current recipe structure on the
HMI device are identical.
Check the specified line/column.
-
-
-
-
-
Select another number.
Check the "ExportDataRecords" system function.
-
-
Check the source of the data record number or data
record name (constant or tag value).
Enter a value within the limits of the recipe tag.
Enter a value within the limits of the recipe tag.
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0