A.2 System alarms
Number
Effect/cause
140007
Tag are not updated or written because the bus
profile is incorrect (see %1).
The following parameter could not be written to the
registry::
1: Tslot
2: Tqui
3: Tset
4: MinTsdr
5: MaxTsdr
6: Trdy
7: Tid1
8: Tid2
9: Gap Factor
10: Retry Limit
140008
No tag updating or writing is executed because
baud rate is incorrect. The following parameters
could not be written to the registry:
0: General error
1: Wrong version
2: Profile cannot be written to the registry.
3: The subnet type cannot be written to the
registry.
4: The Target Rotation Time cannot be written to
the registry.
5: Faulty Highest Address (HSA).
140009
Tags are not updated or written because the
module for S7 communication was not found.
140010
No S7 communication partner found because the
controller is shut down.
DP/T:
The option "PG/PC is the only master" is not set in
the Control Panel under "Set PG/PC interface."
140011
No tag updating or writing is executed because
communication is down.
140012
There is an initialization problem (e.g. when WinCC
flexible Runtime was closed in Task Manager).
Or:
Another application (e.g.STEP7) with different bus
parameters is active and the driver cannot be
started with the new bus parameters (transmission
rate, for example).
140013
The MPI cable is disconnected and, thus, there is
no power supply.
140014
The configured bus address is in already in use by
another application.
140015
Wrong transmission rate
Or:
Faulty bus parameters (e.g.HSA)
Or:
OP address > HSA or: Wrong interrupt vector
(interrupt does not arrive at the driver)
160
Remedy
Check the user-defined bus profile.
Check the connection and if the controller is switched on.
Check the parameter definitions in the Control Panel
using "Set PG/PC interface".
Restart the system.
Check the connection and if the controller is switched on.
Check the parameter definitions in the Control Panel
using "Set PG/PC interface".
Restart the system.
Reinstall the module in the Control Panel using "Set
PG/PC interface".
Switch the controller on.
DP/T:
If only one master is connected to the network, disable
"PG/PC is the only master" in "Set PG/PC interface".
If several masters are connected to the network, enable
these. Do not change any settings, for this will cause bus
errors.
Check the connection and that the communication
partner is switched on.
Restart the HMI device.
Or:
Run WinCC flexible Runtime, then start your other
applications.
Check the connections.
Edit the HMI device address in the controller
configuration.
Correct the relevant parameters.
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0