Number
Effect/cause
290073
An action (e.g. saving a data record) failed due to
an unknown error.
The error corresponds to the status alarm
IDS_OUT_CMD_EXE_ERR in the large recipe
view.
290074
While saving, it was detected that a data record
with the specified number already exists but under
another name.
290075
A data record with this name already exists.
The data record is not saved.
300000
Faulty configuration of process monitoring (e.g.
using PDiag or S7-Graph): More alarms are
queued than specified in the specifications of the
CPU. No further ALARM_S alarms can be
managed by the PLC and reported to the HMI
devices.
300001
ALARM_S is not registered on this controller.
310000
An attempt is being made to print too many reports
in parallel.
Only one log file can be output to the printer at a
given time; the print job is therefore rejected.
310001
An error occurred on triggering the printer. The
report is either not printed or printed with errors.
320000
The movements have already been indicated by
another device.
The movements can no longer be controlled.
320001
The network is too complex.
The faulty addresses cannot be indicated.
320002
No diagnostics alarm selected.
The unit belonging to the alarm could not be
selected.
320003
No alarms exists for the selected unit. The detail
view cannot visualize any networks.
320004
The required signal states could not be read by the
PLC. The faulty addresses cannot be found.
320005
The project contains ProAgent elements which are
not installed. ProAgent diagnostic functions cannot
be performed.
320006
You have attempted to execute a function which is
not supported in the current constellation.
320007
No error-triggering addresses were found on the
networks.
ProAgent cannot indicate any faulty addresses.
320008
The diagnostic data stored in the configuration are
not synchronized with those in the PLC.
ProAgent can only indicate the diagnostic units.
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
Remedy
-
Overwrite the data record, change the data record
number or cancel the action.
Please select a different data record name.
Change the controller configuration.
Select a controller that supports the ALARM_S service.
Wait until the previous active log was printed.
Repeat the print job if necessary.
Evaluate the additional system alarms related to this
alarm.
Repeat the print job if necessary.
Deselect the movements on the other display units and
select the motion control screen on the required display
unit.
View the network in STL.
Select a diagnostics alarm from the ZP_ALARM alarm
screen.
Select the defective unit from the overview screen.
Check the consistency between the configuration on the
display unit and the PLC program.
In order to run the project, install the optional ProAgent
package.
Check the type of the selected unit.
Switch the detail screen to STL layout mode and check
the status of the addresses and exclusion addresses.
Download the project to the HMI device again.
Appendix
A.2 System alarms
173