Appendix
A.2 System alarms
Number
Effect/cause
290007
There is a difference between the source and target
structure of the recipe currently being processed.
The target structure contains an additional data
recipe tag which is not available in the source
structure.
The data recipe tag specified is assigned its start
value.
290008
There is a difference between the source and target
structure of the recipe currently being processed.
The source structure contains an additional data
recipe tag which is not available in the target
structure and therefore cannot be assigned.
The value is rejected.
290010
The storage location configured for the recipe is not
permitted.
Possible causes:
Illegal characters, write protection, data carrier out
of space or does not exist.
290011
The data record with the specified number does not
exist.
290012
The recipe with the specified number does not
exist.
290013
An attempt was made to save a data record under
a data record number which already exists.
The action is not executed.
290014
The file specified to be imported could not be
found.
290020
Message reporting that the download of data
records from the HMI device to the PLC has
started.
290021
Message reporting that the download of data
records from the HMI device to the PLC was
completed.
290022
Message reporting that the download of data
records from the HMI device to the PLC was
canceled due to an error.
290023
Message reporting that the download of data
records from the PLC to the HMI device has
started.
290024
Message reporting that the download of data
records from the PLC to the HMI device was
completed.
170
Remedy
Insert the specified data recipe tag in the source
structure.
Remove the specified data recipe tag in the specified
recipe from the project.
Check the configured storage location.
Check the source for the number (constant or tag value).
Check the source for the number (constant or tag value).
The following remedies are available:
Check the source for the number (constant or tag
value).
First, delete the data record.
Change the "Overwrite" function parameter.
Check:
The file name
Ensure that the file is in the specified directory.
-
-
Check in the configuration whether:
The tag addresses are configured in the controller
The recipe number exists
The data record number exist
The "Overwrite" function parameter is set
-
-
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0