Appendix
A.2 System alarms
Number
Effect/cause
190102
The area pointer is updated after the cause of the
last error state has been eliminated (return to
normal operation). Parameter type and no.: See
alarm 190100.
200000
Coordination is not executed because the address
configured in the controller does not exist/is not set.
200001
Coordination is canceled because the write access
to the address configured in the PLC is not
possible.
200002
Coordination is not carried out at the moment
because the address format of the area pointer
does not match the internal storage format.
200003
Coordination can be executed again because the
last error state is eliminated (return to normal
operation).
200004
The coordination may not be executed.
200005
No more data is read or written. Possible causes:
The cable is defective.
The PLC does not respond, is defective, etc.
System overload.
200100
Coordination is not executed because the address
configured in the controller does not exist/is not set.
200101
Coordination is canceled because the write access
to the address configured in the PLC is not
possible.
200102
Coordination is not carried out at the moment
because the address format of the area pointer
does not match the internal storage format.
200103
Coordination can be executed again because the
last error state is eliminated (return to normal
operation).
200104
The coordination may not be executed.
200105
No more data is read or written. Possible causes:
The cable is defective.
The PLC does not respond, is defective, etc.
System overload.
210000
Jobs are not processed because the address
configured in the controller does not exist/has not
been set up.
210001
Jobs are not processed because read/write access
to the address configured in the controller is not
possible.
210002
Jobs are not executed because the address format
of the area pointer does not match the internal
storage format.
210003
The job buffer is processed again because the last
error status has been eliminated (return to normal
operation).
164
Remedy
-
Change the address or set up the address in the
controller.
Change the address or set the address in the controller at
an area which allows write access.
Internal fault
-
-
Ensure that the cable is plugged in and the controller is
operational.
Restart the system if the system alarm persists.
Change the address or set up the address in the
controller.
Change the address or set the address in the controller at
an area which allows write access.
Internal fault
-
-
Ensure that the cable is plugged in and the controller is
operational.
Restart the system if the system alarm persists.
Change the address or set up the address in the
controller.
Change the address or set up the address in the
controller in an area which allows read/write access.
Internal fault
-
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0