Appendix
A.2 System alarms
Number
Effect/cause
70015
The system time could not be read because
Windows rejects the reading function.
70016
An attempt was made to select a screen by means
of a system function or job. This is not possible
because the screen number specified does not
exist.
Or: A screen could not be generated due to
insufficient system memory.
70017
Date/Time is not read from the area pointer
because the address set in the controller is either
not available or has not been set up.
70018
Acknowledgment that the password list has been
successfully imported.
70019
Acknowledgment that the password list has been
successfully exported.
70020
Acknowledgment for activation of alarm reporting.
70021
Acknowledgment for deactivation of alarm
reporting.
70022
Acknowledgment to starting the Import Password
List action.
70023
Acknowledgment to starting the Export Password
List action.
70024
The value range of the tag has been exceeded in
the system function.
The calculation of the system function is not
performed.
70025
The value range of the tag has been exceeded in
the system function.
The calculation of the system function is not
performed.
70026
No other screens are stored in the internal screen
memory.
No other screens can be selected.
70027
The backup of the RAM file system has been
started.
70028
The files from the RAM have been copied in the
Flash memory.
The files from the RAM have been copied in the
Flash memory. Following a restart, these saved
files are copied back to the RAM file system.
70029
Backup of the RAM file system has failed.
No backup copy of the RAM file system has been
made.
70030
The parameters configured for the system function
are faulty.
The connection to the new controller was not
established.
70031
The controller configured in the system function is
not an S7 controller.
The connection to the new controller was not
established.
154
Remedy
-
Check the screen number in the function or job with the
screen numbers configured.
Assign the number to a screen if necessary.
Change the address or set up the address in the
controller.
-
-
-
-
-
-
Check the desired calculation and correct it if necessary.
Check the desired calculation and correct it if necessary.
-
-
-
Check the settings in the "Control Panel > OP" dialog and
save the RAM file system using the "Save Files" button in
the "Persistent Storage" tab.
Compare the parameters configured for the system
function with the parameters configured for the controllers
and correct them as necessary.
Compare the S7 controller name parameter configured
for the system function with the parameters configured for
the controller and correct them as necessary.
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0