Siemens SIMATIC HMI OP 73micro Operating Instructions Manual page 165

Wincc flexible
Table of Contents

Advertisement

Number
Effect/cause
210004
It is possible that the job buffer will not be
processed.
210005
A control request with an illegal number was
initiated.
210006
An error occurred while attempting to execute the
control request. As a result, the control request is
not executed. Observe the next/previous system
alarms.
220001
The tag is not downloaded because the associated
communication driver / HMI device does not
support the download of Boolean/discrete data
types.
220002
The tag is not downloaded because the associated
communication driver / HMI device does not
support write access to the data type BYTE.
220003
The communication driver cannot be loaded. The
driver may not be installed.
220004
Communication is down and no update data is
transferred because the cable is not connected or
defective etc.
220005
Communication is up.
220006
The connection between the specified PLC and the
specified port is active.
220007
The connection to the specified controller is
interrupted at the specified port.
220008
The communication driver cannot access or open
the specified port. The port may be in use by
another application or the port used is not available
on the destination device.
There is no communication with the controller.
230000
The value entered could not be accepted. The
entered value is discarded and the previous value
is restored.
Either the value range has been exceeded or
impermissible characters were entered.
230002
The currently logged on user is not granted write
access rights. The system therefore discards the
input and restored the previous value.
230003
Changeover to the specified screen failed because
the screen is not available/configured. The current
screen remains selected.
230005
The value range of the tag has been exceeded in
the IO field.
The original value of the tag is retained.
OP 73micro, TP 177micro (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DF01-0AB0
Remedy
-
Check the controller program.
Check the parameters of the control request. Recompile
the configuration.
Change the configuration.
Change the configuration.
Install the driver by reinstalling WinCC flexible Runtime.
Check the connection.
-
-
Check if
the cable is plugged in
the controller is OK
the correct port is used
the configuration is OK (interface parameters, protocol
settings, PLC address).
Restart the system if the system alarm persists.
Close all the applications which access this port and
restart the computer.
Use another port of the system.
Enter a permissible value.
Log on as a user with appropriate rights.
Configure the screen and check the screen selection
function.
Observe the range of values for the tag when entering a
value.
Appendix
A.2 System alarms
165