Parameterizing
7.4
Measurement Range User 1 – 4

Table 28: Overview of adjustable parameters for the user-defined measuring ranges

Parameter
Copy presettings from
Measuring type
Physical conversion
offset
Physical conversion
multiplier
Physical unit string
Enable user scaling
User offset
Description
Here you can select the area from which the settings for this measuring
range should be acquired.
You have the following options:
- Pt 100
- Pt 200
- Pt 500
- Pt 1000
- Ni 100
- Ni 120
- Ni 1000
- 1 kΩ resistance
- 4 kΩ resistance
- Potentiometer %
- User-defined 1
- User-defined 2
- User-defined 3
- User-defined 4
Here you can select the base measuring range of the electronics.
You have the following options:
500 Ω
1 kΩ
2.5 kΩ
5 kΩ
Offset value for calculating the physical value F(x) from the process
value (x).
F(x) = (x + conversion offset) * conversion multiplier.
Conversion factor (gain) for calculating the physical value F(x) from
the process value (x).
F(x) = (x + conversion offset) * conversion multiplier.
Display of the physical measured value.
Here you can activate and deactivate the user scaling ("User Offset"
and "User Gain").
Offset value for scaling the process value.
The process value is calculated according to the following formula:
F(x) = (x + user offset) * user gain
WAGO-SPEEDWAY 767
767-6402 4 AI RTD
Manual
Version 3.1.0