Connecting The Supply Cable; Table 20: Supply Connection Assignment - WAGO 767-6402 Manual

Analog input module rtd
Table of Contents

Advertisement

44
Connecting Data and Supply Cables
Pos : 23.15 /Serie 767 ( WAGO-SPEED WAY)/Ansc hluss D aten- und Versorgungs kabel/I/O-M odule/Ansc hlus s_Spannungs vers orgung allgemein @ 5\mod_1249291817750_21.doc x @ 39906 @ 2 @ 1
5.4

Connecting the Supply Cable

The supply cable provides power to the module.
Requirement:
The WAGO supply cables K1 and K2, which are pre-assembled on both ends,
must be available (see figure on next page).
The following table outlines the assignment of the supply connections:

Table 20: Supply connection assignment

Connection
IN
Pos : 23.16 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sic herheits hinweise/Ac htung/Ac htung: Höchs te Strombel astbar keit der Vers orgungs kontakte @ 8\mod_1278308653219_21.doc x @ 58916 @ @ 1
The highest current carrying capacity of the supply contacts is 4 A!
Always observe the maximum current carrying capacity per supply line (U
for each 767 Series component and the overall power consumption for all
767 components. Neither of these values shall exceed 4 A since an increase in
current causes the contacts to overheat and damages the 767 Series components.
Information regarding the power demand of each 767 Series component can be
found in the corresponding data sheet, which is available from www.wago.com.
Pos : 23.17 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Contact
OUT
1
2
3
4
WAGO-SPEEDWAY 767
767-6402 4 AI RTD
Description
24 VDC U
LS
24 VDC U
A
0 V U
LS
0 V U
A
, U
)
LS
A
Manual
Version 3.1.0

Advertisement

Chapters

Table of Contents
loading

Table of Contents