ROOM UNIT: CONTROL OF SOLAR SySTEM AND ANy ADDITIONAL SySTEMS INSTALLED AS ACCESSORIES
n
When an error
occurs, press the key (6) to display
the error message. The message on the display descri-
bes the cause of the error.
If an error occurs, an alarm may also activate a suitably
configured QX... relay.
This parameter resets the alarm relay.
6710
Alarm relay reset
The difference between the setpoint and the current
temperature is monitored. If this difference persists for
longer than the time set here, the system generates an
error.
6740
CH flow 1 temperature alarm
6741
CH flow 2 temperature alarm
6743
Boiler temperature alarm
The controller memorises the codes and dates for the
last 10 errors.
ERROR TABLE
Error code
0
10
20
25
26
28
30
32
38
40
50
52
57
60
65
68
70
71
73
81
82
83
84
(*) Only with a remote storage cylinder
Description
Description
Description
History...
Solid fuel boiler temperature sensor (not used)
Flow manifold temperature sensor
Primary controller flow temperature sensor
CH return temperature sensor 1
DHW circulation pump temperature sensor (*)
Storage cylinder temperature sensor 1
Storage cylinder temperature sensor 2
Solar collector temperature sensor 1
Error
30: Flow sensor 1
Description
No error
Outside sensor
Attention
Boiler temperature sensor 1
3: Maintenance interval exceeded
Flue gas temperature sensor
CH flow 1 sensor
CH flow 2 sensor
DHW 1 temperature sensor (*)
DHW 2 temperature sensor (*)
Room temperature sensor 1
Room temperature sensor 2
Room temperature sensor P
LPB short circuit
LPB address conflict
BSB short circuit
BSB address conflict
77