Troubleshooting - Riello ALUDOMUS SOLAR KV/200 20 ISC SOLAR Installation And Maintenance Manual

Hide thumbs Also See for ALUDOMUS SOLAR KV/200 20 ISC SOLAR:
Table of Contents

Advertisement

3 . 1 6 Troubleshooting

FAULT
There is a smell of gas.
There is a smell of combustion
fumes
There is condensate on
the flue gas vent pipes
Combustion is uneven
Ignition is slow and the burner
pulses
The boiler gets dirty very quickly
Burner does not ignite
when heat is requested
Boiler does not start up
The boiler does not reach
its temperature setpoint
CAUSE
Leaks from the supply circuit.
Leaks from the flue gas circuit
Low flue gas temperature
Incorrect gas pressure at burner
The wrong diaphragm is installed
Burner and heat exchanger need
cleaning
Heat exchanger pipes obstructed
Incorrect gas pressure at burner
Inefficient combustion
Boiler thermostat or sensor
failure
Safety thermostat tripped
No electrical power
(green LED off).
Heat exchanger dirty
Insufficient air/fuel flow to burner
Boiler settings
111
THECNICAL ASSISTANCE SERVICE
SOLUTION
− Check that all joints are tight and that
the pressure measurement points are
closed
Check:
− - That all joints are tight.
− - That the flues are not obstructed.
− - That combustion is efficient
− Check the combustion
− parameters and the fuel flow
− Check setting
− Check diaphragm diameter
− Check condition
− Check cleanliness of pipes
− Check cleanliness of pipes
− Check colour of flame.
− Check combustion settings
− Check
− Reset
Check:
− electrical connections.
− fuse
− Clean the combustion chamber
− Check and adjust the burner
− Check correct functioning.
− Set the boiler temperature to maxi-
mum