5.2.4
Wiring for Power to Detector Heater
This wiring provides electric power from the converter to the heater for heating the sensor in the
detector.
(1) Ambient temperature of the detector: 75°C or less
ZR22G
Detector
HTR 7
HTR 8
(2) Ambient temperature of the detector: exceeding 75°C
ZR22G
Detector
HTR 7
HTR 8
Figure 5.6
Cable Specifications
Basically, cables (2 cores) that withstand temperatures of at least 80°C are used for this wiring.
When the ambient temperature of the detector exceeds 75°C, install a terminal box, and connect
to the detector using six-piece 600 V silicon rubber insulated glass braided wires.
5.2.5
Wiring for Detector Output
This wiring enables the converter to receive cell output from the detector, output from a
thermocouple and a reference junction compensation signal. Install wires that allow for 10 Ω of
loop resistance or less. Keep detector wiring away from power wiring.
Heat-resistant wiring
Wiring for power to detector heater
<5. Wiring>
ZR402G
Converter
ZR402G
Terminal box
Converter
IM 11M12A01-02E
5-7
HEATER
HEATER
F5-7E.ai
16th Edition : Mar. 19, 2020-00