7-1. Refrigerant Cycle Diagram

RAS-10G2KCVP-T / RAS-10G2ACVP-T
RAS-13G2KCVP-T / RAS-13G2ACVP-T
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 9.52mm
Thickness : 0.8mm
Temp. measurement
NOTE :
• The maximum pipe length of this air conditioner is 20m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
7. REFRIGERANT CYCLE DIAGRAM
INDOOR UNIT
Cross flow fan
Deoxidized copper pipe
Sectional shape
of heat insulator
TS
Compressor
DA108X1C-23FZ
TD
Muffler
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
Temp. measurement
T1
TCJ
Indoor heat
exchanger
TC
TA
Outer dia. : 6.35mm
Thickness : 0.8mm
TO
Split capillary
Ø1.2 x 80s
Ø1.2 x 80s
- 20 -
FILE NO. SVM-15058
Max.
Min.
Chargeless : 15m
Charge : 20g/m
(16 to 20m)
Strainer
Pulse Modulating
valve at liquid side
Refrigerant amount : 1.10kg
NOTE :
Gas leak check position
Refrigerant flow
: 20m
: 1m