Toshiba RAS-13G2KCVP-T Service Manual page 68

Table of Contents

Advertisement

10-4. Outdoor Unit
10-4-1. Installation Place
• A place which provides enough space around the
outdoor unit as shown in the diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb neighbors.
• A place which is not exposed to a strong wind.
• A place free of combustible gases.
• A place which does not block a passageway.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length & height, please refer from
1. SPECIFICATIONS.
A place where the drain water does not cause any
problems.
Precautions for adding refrigerant
• Use a scale having a precision with at least 10 g
per index line when adding the refrigerant.
Do not use a bathroom scale or similar instrument.
• Use liquid refrigerant when refilling the refrigerant.
Since the refrigerant is in liquid form, it can fill
quickly.
Therefore, perform the filling operation carefully
and insert the refrigerant gradually.
1. Install the outdoor unit without anything
blocking the discharging air.
2. When the outdoor unit is installed in a place
always exposed to strong winds like on the
coast or on a high story of a building, secure
the normal fan operation using a duct or a
wind shield.
3. Especially in windy areas, install the unit to
prevent the admission of wind.
4. Installation in the following places may result
in trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are
likely to be generated, such as from audio
equipment, welders, and medical equip-
ment.
10-4-2. Refrigerant Piping Connection
Flaring
1. Cut the pipe with a pipe cutter.
2. Deburr the inside of the pipe at its end.
Take steps to ensure that the removed burrs will not enter the pipe.
3. Remove the fl are nuts provided with the indoor and outdoor units, and
insert them into the pipe.
4. Flare the pipe.
The projection margin of the pipe must be checked.
5. Check that the ß are has the appropriate shape.
90
A
Die
Pipe
Pipe
Rigid
Outside
Thickness
(clutch type)
diameter
R410A tool
mm
mm
mm
6.35
0.8
0 to 0.5
9.52
0.8
0 to 0.5
12.7
0.8
0 to 0.5
- 68 -
FILE NO. SVM-15058
CAUTION
Strong
wind
Fig. 10-4-1
Obliquity
Roughness
B
C
A
B
Flare Nut
Imperial
(wing nut
C
Tighten torque
type)
R410A tool
mm
mm
mm
N·m
1.5 to 2.0
9.1
17
14 to 18
1.5 to 2.0
13.2
22
33 to 42
2.0 to 2.5
16.6
26
50 to 62
Warp
kgf·m
1.4 to 1.8
3.3 to 4.2
5.0 to 6.2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents