Pulse Modulating Valve (P.m.v.) Control - Toshiba RAS-13G2KCVP-T Service Manual

Table of Contents

Advertisement

Item
12. Pulse
This function controls throttle amount of the
Modulating
refrigerant in the refrigerating cycle.
valve (P.M.V.)
According to operating status of the air conditioner,
control
this function also controls the open degree of valve
with an expansion valve with pulse Modulation.
Starting up
Initialize
Move to
initial position
SH control
PMV open degree control
Compressor Stop by
Turn OFF by
"Room Temperature
remote controller
Move to "Stop
Position" (Setup
from factory)
* SH (Super Heat amount) =
Ts (Temperature of suction pipe of the compressor) –
Tc or Te (Heat exchanger temperature at evaporation side)
* PMV: Pulse Modulating Valve
Operation flow and applicable data, etc.
Compressor ON
Td, high pressure
release control
Defrosting
operation
Control"
Move to "Defrost
Position" (Setup
from factory)
1) When starting the operation, move the
valve once until it fits to the stopper.
(Initialize)
* In this time, "Click" sound may be
heard.
2) Adjust the open degree of valve by super
heat amount. (SH control)
3) If the discharge temperature was exces-
sively up, adjust the open degree of valve
so that it is in the range of set tempera-
ture. (Discharge temp. control)
4) When operation is OFF by the remote
controller or when compressor is OFF by
room temperature control, the open
degree of valve is adjusted to the stop
position.
- 40 -
FILE NO. SVM-15058