<In cooling/dry operation>
temperature
(Prevent-freezing control for indoor heat exchanger)
release
In cooling/dry operation, the sensor of indoor heat exchanger detects
protective
evaporation temperature and controls the compressor speed so that
control by
temperature
temperature of the heat exchanger does not exceed the specifi ed
of indoor heat
value.
exchanger
7˚C
6˚C
5˚C
Operation flow and applicable data, etc.
Usual cooling capacity control
Reduction of compressor speed
R
When the value is
in Q zone, the
Q
compressor speed
is kept.
P
- 33 -
FILE NO. SVM-15058
Description
1 When temperature of the
exchanger drops below
5°C, the compressor speed
is reduced. (P zone)
2 When temperature of the
indoor heat exchanger rises
exchanger rises in the range
from 6°C to under 7°C, the
compressor speed is kept.
(Q zone)
3 When temperature of the
indoor heat exchanger rises
to 7°C or higher, the
capacity control operation
returns to the usual control
in cooling operation.
(R zone)